Uninterruptible power sources of LP 33 series with three-phase input/output produced by GE Digital Energy is highly reliable and economic three-phase systems providing electric power supply protection for critical load of wide range.
Product catalog











Latest News and Actions
Last articles
Last gallerys
All UPS of LP 33 series operate in VFI mode (Voltage & Frequency Independent) ensuring maximal electric power supply reliability level for critical processes.
LP 33 series is developed on the basis of Six Sigma Methodology that ensures absolute meeting wit requirements of any consumer.
The unique technology of Redundant Parallel Architecture ™ (RPA™) elaborated by GE Company allows cranking up and improving the system reliability due to installation of additional UPS units creating therefore the system where non-reserved failure points are absent. The UPSes of LP 10-40 series operate up to 4 devices in parallel.
Features and Benefits
- Small dimensions, easy transporting
- The low distortion level at the input makes use of expensive filters or overshoot of generator power unnecessary
- Advanced technology providing almost noiseless operation
- High output power factor makes it possible to avoid UPS power overshoot in calculations
- Meets the strictest requirements of providing minimal distortion level of output voltage
- Superior Battery Management System (SBM) prolongs life time of the batteries and prevent failure arising
- ECO-mode reduces electric energy consumption in conditions of stable network in automatic mode
- Monitoring and protection software
Fields of application
- Communications nodes
- Computation centers and data processing and storage centers
- Equipment for industrial processes control
- Medical equipment and public health care establishments
- Broadcasting and satellite communication systems
- Transport
- Stationary and mobile systems of voice connection systems and data transfer systems
- Emergency alarm systems
- Security and safety systems
- Financial systems and services
LP10-33
|
LP20-33
|
LP30-33
|
LP40-33
|
Model
LP10-33
UPS: | ![]() |
three-phase UPS |
Output power (kVА) at cos? = 0.6-0.8: | ![]() |
10 |
Output power (kW): | ![]() |
10 |
Output power factor (cos?): | ![]() |
1 |
Standard autonomy time at 50 / 100% load (min): | ![]() |
26/10 |
Charging rate (А): | ![]() |
1,4 |
Additional charging device 4.2А: | ![]() |
+ |
Dimensions (HхWхD): | ![]() |
500х780х1320 mm |
Weight (kg): | ![]() |
270 (batteries 7 Аh.) - 370 (batteries 14 Аh.) |
Noise level (dB (A)): | ![]() |
53 |
Efficiency coefficient: | ![]() |
91,1 |
Efficiency coefficient in ECO-mode: | ![]() |
98,2 |
Protection class: | ![]() |
IP20 |
Parallel operation: | ![]() |
up to 4 devices |
Input voltage range (V): | ![]() |
320 – 460 V |
Input frequency range (Hz): | ![]() |
50/60 Hz + / -10% |
Input power factor (cos?): | ![]() |
0,98 |
Input current distortion (THD) at the load of 20%-100%: | ![]() |
< 8% |
Output voltage (V): | ![]() |
3 х 380 / 400 / 415 В + N (selected by user) |
Output frequency (Hz): | ![]() |
50/60 Hz + / - 0.1% |
Output voltage distortion (THD) at linear load: | ![]() |
< 2% |
Output voltage distortion (THD) at non-linear load: | ![]() |
< 3% |
Output voltage constancy at static load: | ![]() |
< +/-1% |
Output voltage constancy at dynamic load (alternation - 100%): | ![]() |
< +/-3% (restoration time < 20ms) |
Inverter overload capability: | ![]() |
125% - 10 min., 150% - 1 min. |
Environment operating temperature: | ![]() |
UPS: 0-40 ?C; Battery: 20-25 ?C |
Humidity: | ![]() |
95% without condensate |
Safety standards: | ![]() |
EN 50091 / EN/IEC 62040, CE marking |
EMC standard: | ![]() |
EN 50091-2; EN/IEC 62040-2 Class A |
Standard interface: | ![]() |
RS232, dry-type contacts |
Advanced battery control: | ![]() |
+ |
Options: | ![]() |
RPA, SNMP-card, additional battery enclosures |