SG60
Type of UPS: |
 |
three-phase UPS 380V |
Output power (kVA): |
 |
40 kVA |
Output power (kW): |
 |
40 kW |
Output power factor cos?: |
 |
1 |
Rectifier: |
 |
IGBT Pure Pulse® |
Dimensions of UPS power module (WхDхH, mm): |
 |
680 х 800 х 1450 |
Dimensions of a standard battery cabinet for 8-11 min. at 100% load (WхDхH, mm): |
 |
battery in UPS |
Weight (kg): |
 |
400 |
Noise level (dB(А)): |
 |
< 65 |
Efficiency coefficient in Super ECO mode: |
 |
up to 98,4 % |
Coefficient of performance (%): |
 |
92,3 |
Parallel work: |
 |
up to 6 UPS |
Protection class: |
 |
IP 20 |
Input voltage range: |
 |
340-460 V |
Input frequency range: |
 |
45-66 Hz |
Input harmonic distortions THD: |
 |
<2% (using IGBT-rectifier with PurePulse Technology) |
Output voltage: |
 |
3 х 380/400/415V, selected by user) |
Output frequency: |
 |
50/60 Hz + - 0.1% |
Output harmonic distortions THD at linear load: |
 |
<2% |
Output harmonic distortions THD at non-linear load: |
 |
<3% |
Relative humidity: |
 |
95% without condensate |
Stability of output voltage: |
 |
+- 1% |
Stability of output voltage at dynamic load (alternation 100%): |
 |
<+ - 2% (recovery time <5 msec.) |
Overload capability of inverter: |
 |
125% - 10 min., 150% - 1 min. |
Environment operating temperature: |
 |
0 - 40 °C |
Color: |
 |
RAL 9003 white |
Safety standards: |
 |
ENIEC 62040-1-1 |
EMC standards: |
 |
ENIEC 62040-2 (Class A) | |
SG80
Type of UPS: |
 |
three-phase power supply 380V |
Output power (kVA): |
 |
80 kVA |
Output power (kW): |
 |
72 kW |
Output power factor cos?: |
 |
0,9 |
Rectifier: |
 |
IGBT Pure Pulse® |
Dimensions of UPS power module (WхDхH, mm): |
 |
650 х 850 х 1900 |
Dimensions of a standard battery cabinet for 8-11 min. at 100% load (WхDхH, mm): |
 |
850 х 850 х 1900 |
Weight (kg): |
 |
630 |
Noise level (dB(А)): |
 |
< 65 |
Efficiency coefficient in Super ECO mode: |
 |
up to 98,4 % |
Coefficient of performance (%): |
 |
91,2 |
Parallel work: |
 |
up to 6 UPS |
Protection class: |
 |
IP 20 |
Input voltage range: |
 |
340-460 V |
Input frequency range: |
 |
45-66 Hz |
Input harmonic distortions THD: |
 |
<2% (using IGBT-rectifier with PurePulse Technology) |
Output voltage: |
 |
3 х 380/400/415V, selected by user) |
Output frequency: |
 |
50/60 Hz + - 0.1% |
Output harmonic distortions THD at linear load: |
 |
<1.5% |
Output harmonic distortions THD at non-linear load: |
 |
<3% |
Relative humidity: |
 |
95% without condensate |
Stability of output voltage: |
 |
+- 1% |
Stability of output voltage at dynamic load (alternation 100%): |
 |
<+ - 2% (recovery time <5 msec.) |
Overload capability of inverter: |
 |
125% - 10 min., 150% - 1 min. |
Environment operating temperature: |
 |
0 - 40 °C |
Color: |
 |
RAL 9003 white |
Safety standards: |
 |
ENIEC 62040-1-1 |
EMC standards: |
 |
ENIEC 62040-2 (Class A) | |
SG100
Type of UPS: |
 |
UPS three-phase 380V |
Output power (kVA): |
 |
100 kVA |
Output power (kW): |
 |
90 kW |
Output power factor cos?: |
 |
0,9 |
Rectifier: |
 |
IGBT Pure Pulse® |
Dimensions of UPS power module (WхDхH, mm): |
 |
835 х850 х 1900 |
Dimensions of a standard battery cabinet for 8-11 min. at 100% load (WхDхH, mm): |
 |
850 х 850 х 1900 |
Weight (kg): |
 |
860 |
Noise level (dB(А)): |
 |
< 65 |
Efficiency coefficient in Super ECO mode: |
 |
up to 98,4 % |
Coefficient of performance (%): |
 |
91,7 |
Parallel work: |
 |
up to 6 UPS |
Protection class: |
 |
IP 20 |
Input voltage range: |
 |
340-460 V |
Input frequency range: |
 |
45-66 Hz |
Input harmonic distortions THD: |
 |
<2% (using IGBT-rectifier with PurePulse Technology) |
Output voltage: |
 |
3 х 380/400/415V, selected by user) |
Output frequency: |
 |
50/60 Hz + - 0.1% |
Output harmonic distortions THD at linear load: |
 |
<1.5% |
Output harmonic distortions THD at non-linear load: |
 |
<3% |
Relative humidity: |
 |
95% without condensate |
Stability of output voltage: |
 |
+- 1% |
Stability of output voltage at dynamic load (alternation 100%): |
 |
<+ - 2% (recovery time <5 msec.) |
Overload capability of inverter: |
 |
125% - 10 min., 150% - 1 min. |
Environment operating temperature: |
 |
0 - 40 °C |
Color: |
 |
RAL 9003 white |
Safety standards: |
 |
ENIEC 62040-1-1 |
EMC standards: |
 |
ENIEC 62040-2 (Class A) | |
SG120
Type of UPS: |
 |
three-phase UPS 380V |
Output power (kVA): |
 |
120 kVA |
Output power (kW): |
 |
90 kW |
Output power factor cos?: |
 |
0,9 |
Rectifier: |
 |
IGBT Pure Pulse® |
Dimensions of UPS power module (WхDхH, mm): |
 |
835 х 850 х 1900 |
Dimensions of a standard battery cabinet for 8-11 min. at 100% load (WхDхH, mm): |
 |
850 х 850 х 1900 |
Weight (kg): |
 |
860 |
Noise level (dB(А)): |
 |
< 65 |
Efficiency coefficient in Super ECO mode: |
 |
up to 98,4 % |
Coefficient of performance (%): |
 |
91,2 |
Parallel work: |
 |
up to 6 UPS |
Protection class: |
 |
IP 20 |
Input voltage range: |
 |
340-460 V |
Input frequency range: |
 |
45-66 Hz |
Input harmonic distortions THD: |
 |
<2% (using IGBT-rectifier with PurePulse Technology) |
Output voltage: |
 |
3 х 380/400/415V, selected by user) |
Output frequency: |
 |
50/60 Hz + - 0.1% |
Output harmonic distortions THD at linear load: |
 |
<1.5% |
Output harmonic distortions THD at non-linear load: |
 |
<3% |
Relative humidity: |
 |
95% without condensate |
Stability of output voltage: |
 |
+- 1% |
Stability of output voltage at dynamic load (alternation 100%): |
 |
<+ - 2% (recovery time <5 msec.) |
Overload capability of inverter: |
 |
125% - 10 min., 150% - 1 min. |
Environment operating temperature: |
 |
0 - 40 °C |
Color: |
 |
RAL 9003 white |
Safety standards: |
 |
ENIEC 62040-1-1 |
EMC standards: |
 |
ENIEC 62040-2 (Class A) | |
SG160
Type of UPS: |
 |
three-phase power supply 380V |
Output power (kVA): |
 |
160 kVA |
Output power (kW): |
 |
144 kW |
Output power factor cos?: |
 |
0,9 |
Rectifier: |
 |
IGBT Pure Pulse ® / Thyristor |
Dimensions of UPS power module (WхDхH, mm): |
 |
1350 х 850 х 1900 |
Dimensions of a standard battery cabinet for 8-11 min. at 100% load (WхDхH, mm): |
 |
|
Weight (kg): |
 |
1100 / 1225 |
Noise level (dB(А)): |
 |
< 69 |
Efficiency coefficient in Super ECO mode: |
 |
up to 98,4 % |
Coefficient of performance (%): |
 |
92,8 |
Parallel work: |
 |
up to 6 UPS |
Protection class: |
 |
IP 20 |
Input voltage range: |
 |
340-460 V |
Input frequency range: |
 |
45-66 Hz |
Input harmonic distortions THD: |
 |
<2% (using IGBT-rectifier with PurePulse Technology) |
Output voltage: |
 |
3 х 380/400/415V, selected by user) |
Output frequency: |
 |
50/60 Hz + - 0.1% |
Output harmonic distortions THD at linear load: |
 |
<1.5% |
Output harmonic distortions THD at non-linear load: |
 |
<3% |
Relative humidity: |
 |
95% without condensate |
Stability of output voltage: |
 |
+- 1% |
Stability of output voltage at dynamic load (alternation 100%): |
 |
<+ - 2% (recovery time <5 msec.) |
Overload capability of inverter: |
 |
125% - 10 min., 150% - 1 min. |
Color: |
 |
RAL 9003 white |
Safety standards: |
 |
ENIEC 62040-1-1 |
EMC standards: |
 |
ENIEC 62040-2 (Class A) | |
SG200
Type of UPS: |
 |
UPS three-phase 380V |
Output power (kVA): |
 |
200 kVA |
Output power (kW): |
 |
180 kW |
Output power factor cos?: |
 |
0,9 |
Rectifier: |
 |
IGBT Pure Pulse ® / Thyristor |
Dimensions of UPS power module (WхDхH, mm): |
 |
1350 х 850 х 1900 |
Weight (kg): |
 |
1150 / 1315 |
Noise level (dB(А)): |
 |
< 69 |
Efficiency coefficient in Super ECO mode: |
 |
up to 98,4 % |
Coefficient of performance (%): |
 |
93,2 |
Parallel work: |
 |
up to 6 UPS |
Protection class: |
 |
IP 20 |
Input voltage range: |
 |
340-460 V |
Input frequency range: |
 |
45-66 Hz |
Input harmonic distortions THD: |
 |
<2% (using IGBT-rectifier with PurePulse Technology) |
Output voltage: |
 |
3 х 380/400/415V, selected by user) |
Output frequency: |
 |
50/60 Hz + - 0.1% |
Output harmonic distortions THD at linear load: |
 |
<1.5% |
Output harmonic distortions THD at non-linear load: |
 |
<3% |
Relative humidity: |
 |
95% without condensate |
Stability of output voltage: |
 |
+- 1% |
Stability of output voltage at dynamic load (alternation 100%): |
 |
<+ - 2% (recovery time <5 msec.) |
Overload capability of inverter: |
 |
125% - 10 min., 150% - 1 min. |
Environment operating temperature: |
 |
0 - 40 °C |
Color: |
 |
RAL 9003 white |
Safety standards: |
 |
ENIEC 62040-1-1 |
EMC standards: |
 |
ENIEC 62040-2 (Class A) | |
SG250
Type of UPS: |
 |
three-phase UPS 380V |
Output power (kVA): |
 |
250 kVA |
Output power (kW): |
 |
225 kW |
Rectifier: |
 |
IGBT Pure Pulse ® / Thyristor |
Dimensions of UPS power module (WхDхH, mm): |
 |
1500 х 850 х 1900 |
Dimensions of a standard battery cabinet for 8-11 min. at 100% load (WхDхH, mm): |
 |
|
Weight (kg): |
 |
1400 / 1675 |
Noise level (dB(А)): |
 |
< 69 |
Efficiency coefficient in Super ECO mode: |
 |
up to 98,4 % |
Parallel work: |
 |
up to 6 UPS |
Protection class: |
 |
IP 20 |
Input voltage range: |
 |
340-460 V |
Input frequency range: |
 |
45-66 Hz |
Input harmonic distortions THD: |
 |
<2% (using IGBT-rectifier with PurePulse Technology) |
Output voltage: |
 |
3 х 380/400/415V, selected by user) |
Output frequency: |
 |
50/60 Hz + - 0.1% |
Output harmonic distortions THD at linear load: |
 |
<1.5% |
Output harmonic distortions THD at non-linear load: |
 |
<3% |
Relative humidity: |
 |
95% without condensate |
Stability of output voltage: |
 |
+- 1% |
Stability of output voltage at dynamic load (alternation 100%): |
 |
<+ - 2% (recovery time <5 msec.) |
Overload capability of inverter: |
 |
125% - 10 min., 150% - 1 min. |
Environment operating temperature: |
 |
0 - 40 °C |
Color: |
 |
RAL 9003 white |
Safety standards: |
 |
ENIEC 62040-1-1 |
EMC standards: |
 |
ENIEC 62040-2 (Class A) | |
SG300
Type of UPS: |
 |
three-phase power supply 380V |
Output power (kVA): |
 |
300 kVA |
Output power (kW): |
 |
270 kW |
Output power factor cos?: |
 |
0,9 |
Rectifier: |
 |
IGBT Pure Pulse ® / Thyristor |
Dimensions of UPS power module (WхDхH, mm): |
 |
1500 х 850 х 1900 |
Weight (kg): |
 |
1450 / 1775 |
Noise level (dB(А)): |
 |
< 69 |
Efficiency coefficient in Super ECO mode: |
 |
up to 98,4 % |
Coefficient of performance (%): |
 |
93,3 |
Parallel work: |
 |
up to 6 UPS |
Protection class: |
 |
IP 20 |
Input voltage range: |
 |
340-460 V |
Input frequency range: |
 |
45-66 Hz |
Input harmonic distortions THD: |
 |
<2% (using IGBT-rectifier with PurePulse Technology) |
Output voltage: |
 |
3 х 380/400/415V, selected by user) |
Output frequency: |
 |
50/60 Hz + - 0.1% |
Output harmonic distortions THD at linear load: |
 |
<1.5% |
Output harmonic distortions THD at non-linear load: |
 |
<3% |
Relative humidity: |
 |
95% without condensate |
Stability of output voltage: |
 |
+- 1% |
Stability of output voltage at dynamic load (alternation 100%): |
 |
<+ - 2% (recovery time <5 msec.) |
Overload capability of inverter: |
 |
125% - 10 min., 150% - 1 min. |
Environment operating temperature: |
 |
0 - 40 °C |
Color: |
 |
RAL 9003 white |
Safety standards: |
 |
ENIEC 62040-1-1 |
EMC standards: |
 |
ENIEC 62040-2 (Class A) | |
SG400
Type of UPS: |
 |
UPS three-phase 380V |
Output power (kVA): |
 |
400 kVA |
Output power (kW): |
 |
360 kW |
Output power factor cos?: |
 |
0,9 |
Rectifier: |
 |
IGBT Pure Pulse® |
Dimensions of UPS power module (WхDхH, mm): |
 |
1800 х 950 х 1900 |
Weight (kg): |
 |
2280 |
Noise level (dB(А)): |
 |
< 72 |
Efficiency coefficient in Super ECO mode: |
 |
up to 98,4 % |
Coefficient of performance (%): |
 |
92,7 |
Parallel work: |
 |
up to 6 UPS |
Protection class: |
 |
IP 20 |
Input voltage range: |
 |
340-460 V |
Input frequency range: |
 |
45-66 Hz |
Input harmonic distortions THD: |
 |
<2% (using IGBT-rectifier with PurePulse Technology) |
Output voltage: |
 |
3 х 380/400/415V, selected by user) |
Output frequency: |
 |
50/60 Hz + - 0.1% |
Output harmonic distortions THD at linear load: |
 |
<1.5% |
Output harmonic distortions THD at non-linear load: |
 |
<3% |
Relative humidity: |
 |
95% without condensate |
Stability of output voltage: |
 |
+- 1% |
Stability of output voltage at dynamic load (alternation 100%): |
 |
<+ - 3% (recovery time <20 msec.) |
Overload capability of inverter: |
 |
125% - 10 min., 150% - 30 sec. |
Environment operating temperature: |
 |
0 - 40 °C |
Color: |
 |
RAL 9003 white |
Safety standards: |
 |
ENIEC 62040-1-1 |
EMC standards: |
 |
ENIEC 62040-2 (Class A) | |
SG500
Type of UPS: |
 |
three-phase UPS 380V |
Output power (kVA): |
 |
500 kVA |
Output power (kW): |
 |
450 kW |
Output power factor cos?: |
 |
0,9 |
Rectifier: |
 |
IGBT Pure Pulse® |
Dimensions of UPS power module (WхDхH, mm): |
 |
1800 х 950 х 1900 |
Weight (kg): |
 |
2550 |
Noise level (dB(А)): |
 |
< 72 |
Efficiency coefficient in Super ECO mode: |
 |
up to 98,4 % |
Coefficient of performance (%): |
 |
92,5 |
Parallel work: |
 |
up to 6 UPS |
Protection class: |
 |
IP 20 |
Input voltage range: |
 |
340-460 V |
Input frequency range: |
 |
45-66 Hz |
Input harmonic distortions THD: |
 |
<2% (using IGBT-rectifier with PurePulse Technology) |
Output voltage: |
 |
3 х 380/400/415V, selected by user) |
Output frequency: |
 |
50/60 Hz + - 0.1% |
Output harmonic distortions THD at linear load: |
 |
<1.5% |
Output harmonic distortions THD at non-linear load: |
 |
<3% |
Relative humidity: |
 |
95% without condensate |
Stability of output voltage: |
 |
+- 1% |
Stability of output voltage at dynamic load (alternation 100%): |
 |
<+ - 3% (recovery time <20 msec.) |
Overload capability of inverter: |
 |
125% - 10 min., 150% - 30 sec. |
Environment operating temperature: |
 |
0 - 40 °C |
Color: |
 |
RAL 9003 white |
Safety standards: |
 |
ENIEC 62040-1-1 |
EMC standards: |
 |
ENIEC 62040-2 (Class A) | |