25А
3-pole, floor-mounted cabinet (H х W х D), mm: |
|
1100 x 800 x 400 |
3-pole, 19’’ case (H х W х D), mm: |
|
710 x 483 x 465 |
4-pole, floor-mounted cabinet (H х W х G), mm: |
|
1100 x 800 x 400 |
4-pole, 19’’ (H х W х D), mm: |
|
710 x 483 x 465 |
Weight (approximatey), kg: |
|
60 |
Color: |
|
RAL 7032 |
Rated input voltage: |
|
3 х 400 V |
Input voltage range: |
|
-25% / +20% |
Rated frequency: |
|
50 Hz |
Frequency range: |
|
-9% / +6% |
Efficiency coefficient: |
|
> 99% at cos? = 0,8 |
Allowable cross ratio: |
|
3,5 : 1 |
Power factor (max. cos?): |
|
0.5 – 1.0 (delay /advance) |
Overload capability: |
|
125% - hour, 400% - 5 seconds, 800% - 0.4 sec, 1000% - 0.2 sec, 1500% - 20 msec |
Short circuit current: |
|
32 kA |
Time of switch (manual /automatic): |
|
<0.1 ms / <6 ms (typical 3 ms) |
Level of increased voltage: |
|
+ 6 / 9 / 13 / 16 / 20% |
Level of decreased voltage: |
|
- 8 / 12 / 16 / 20 / 24% |
Phase difference (for synchronized inputs): |
|
8 / 12 / 16 / 20 / 24 degrees |
Switch at current overload: |
|
block is absent / 3 / 4,5 / 6 / 7,5 / 9-fold overload |
Switch delay (without synchronization): |
|
13 / 17 / 25 / 50 msec |
Delay of reset to priority input: |
|
0,8 / 1 / 8 / 25 sec |
Conditions: Temperature |
|
0 - 40°C |
Conditions: Relative humidity |
|
<95% without condensation |
Conditions: Level above sea |
|
1000 m (more than 1000 m power reduce by 5%) / 500 m / not more than 3000 m |
Conditions: Cooling |
|
back-up fans |
Conditions: Noise level |
|
<55 dBA |
Conditions: IEC |
|
EN50022 level B, EN60555-23 |
Conditions: Design |
|
IP20 (floor-mounted cabinets), IP00 (19’’ case) |
Alarm: Dry contacts |
|
300 V or 250 V-/ 0,3 A = 4 or A-(at 220) |
Alarm: Status Information |
|
manual switch, return blockage, main/back-up input ОК, main/back-up input ON |
Alarm: Notifications |
|
main/back-up of input out of tolerance, no synchronization, manual mode |
Alarm: Emergency alarms |
|
overload, overheat, fuse actuated, internal accident of STS | |
40А
3-pole, floor-mounted cabinet (H х W х D), mm: |
|
1100 x 800 x 400 |
3-pole, 19’’ case (H х W х D), mm: |
|
710 x 483 x 465 |
4-pole, floor-mounted cabinet (H х W х G), mm: |
|
1100 x 800 x 400 |
4-pole, 19’’ (H х W х D), mm: |
|
710 x 483 x 465 |
Weight (approximatey), kg: |
|
68 |
Color: |
|
RAL 7032 |
Rated input voltage: |
|
3 х 400 V |
Input voltage range: |
|
-25% / +20% |
Rated frequency: |
|
50 Hz |
Frequency range: |
|
-9% / +6% |
Efficiency coefficient: |
|
> 99% at cos? = 0,8 |
Allowable cross ratio: |
|
3,5 : 1 |
Power factor (max. cos?): |
|
0.5 – 1.0 (delay /advance) |
Overload capability: |
|
125% - hour, 400% - 5 seconds, 800% - 0.4 sec, 1000% - 0.2 sec, 1500% - 20 msec |
Short circuit current: |
|
32 kA |
Time of switch (manual /automatic): |
|
<0.1 ms / <6 ms (typical 3 ms) |
Level of increased voltage: |
|
+ 6 / 9 / 13 / 16 / 20% |
Level of decreased voltage: |
|
- 8 / 12 / 16 / 20 / 24% |
Phase difference (for synchronized inputs): |
|
8 / 12 / 16 / 20 / 24 degrees |
Switch at current overload: |
|
block is absent / 3 / 4,5 / 6 / 7,5 / 9-fold overload |
Switch delay (without synchronization): |
|
13 / 17 / 25 / 50 msec |
Delay of reset to priority input: |
|
0,8 / 1 / 8 / 25 sec |
Conditions: Temperature |
|
0 - 40°C |
Conditions: Relative humidity |
|
<95% without condensation |
Conditions: Level above sea |
|
1000 m (more than 1000 m power reduce by 5%) / 500 m / not more than 3000 m |
Conditions: Cooling |
|
back-up fans |
Conditions: Noise level |
|
<55 dBA |
Conditions: IEC |
|
EN50022 level B, EN60555-23 |
Conditions: Design |
|
IP20 (floor-mounted cabinets), IP00 (19’’ case) |
Alarm: Dry contacts |
|
300 V or 250 V-/ 0,3 A = 4 or A-(at 220) |
Alarm: Status Information |
|
manual switch, return blockage, main/back-up input ОК, main/back-up input ON |
Alarm: Notifications |
|
main/back-up of input out of tolerance, no synchronization, manual mode |
Alarm: Emergency alarms |
|
overload, overheat, fuse actuated, internal accident of STS | |
63А
3-pole, floor-mounted cabinet (H х W х D), mm: |
|
1100 x 800 x 400 |
3-pole, 19’’ case (H х W х D), mm: |
|
710 x 483 x 465 |
4-pole, floor-mounted cabinet (H х W х G), mm: |
|
1100 x 800 x 400 |
4-pole, 19’’ (H х W х D), mm: |
|
710 x 483 x 465 |
Weight (approximatey), kg: |
|
72 |
Color: |
|
RAL 7032 |
Rated input voltage: |
|
3 х 400 V |
Input voltage range: |
|
-25% / +20% |
Rated frequency: |
|
50 Hz |
Frequency range: |
|
-9% / +6% |
Efficiency coefficient: |
|
> 99% at cos? = 0,8 |
Allowable cross ratio: |
|
3,5 : 1 |
Power factor (max. cos?): |
|
0.5 – 1.0 (delay /advance) |
Overload capability: |
|
125% - hour, 400% - 5 seconds, 800% - 0.4 sec, 1000% - 0.2 sec, 1500% - 20 msec |
Short circuit current: |
|
32 kA |
Time of switch (manual /automatic): |
|
<0.1 ms / <6 ms (typical 3 ms) |
Level of increased voltage: |
|
+ 6 / 9 / 13 / 16 / 20% |
Level of decreased voltage: |
|
- 8 / 12 / 16 / 20 / 24% |
Phase difference (for synchronized inputs): |
|
8 / 12 / 16 / 20 / 24 degrees |
Switch at current overload: |
|
block is absent / 3 / 4,5 / 6 / 7,5 / 9-fold overload |
Switch delay (without synchronization): |
|
13 / 17 / 25 / 50 msec |
Delay of reset to priority input: |
|
0,8 / 1 / 8 / 25 sec |
Conditions: Temperature |
|
0 - 40°C |
Conditions: Relative humidity |
|
<95% without condensation |
Conditions: Level above sea |
|
1000 m (more than 1000 m power reduce by 5%) / 500 m / not more than 3000 m |
Conditions: Cooling |
|
back-up fans |
Conditions: Noise level |
|
<55 dBA |
Conditions: IEC |
|
EN50022 level B, EN60555-23 |
Conditions: Design |
|
IP20 (floor-mounted cabinets), IP00 (19’’ case) |
Alarm: Dry contacts |
|
300 V or 250 V-/ 0,3 A = 4 or A-(at 220) |
Alarm: Status Information |
|
manual switch, return blockage, main/back-up input ОК, main/back-up input ON |
Alarm: Notifications |
|
main/back-up of input out of tolerance, no synchronization, manual mode |
Alarm: Emergency alarms |
|
overload, overheat, fuse actuated, internal accident of STS | |
100А
3-pole, floor-mounted cabinet (H х W х D), mm: |
|
1100 x 800 x 400 |
3-pole, 19’’ case (H х W х D), mm: |
|
710 x 483 x 465 |
4-pole, floor-mounted cabinet (H х W х G), mm: |
|
1900 x 800 x 500 |
4-pole, 19’’ (H х W х D), mm: |
|
710 x 483 x 465 |
Weight (approximatey), kg: |
|
195 |
Color: |
|
RAL 7032 |
Rated input voltage: |
|
3 х 400 V |
Input voltage range: |
|
-25% / +20% |
Rated frequency: |
|
50 Hz |
Frequency range: |
|
-9% / +6% |
Efficiency coefficient: |
|
> 99% at cos? = 0,8 |
Allowable cross ratio: |
|
3,5 : 1 |
Power factor (max. cos?): |
|
0.5 – 1.0 (delay /advance) |
Overload capability: |
|
125% - hour, 400% - 5 seconds, 800% - 0.4 sec, 1000% - 0.2 sec, 1500% - 20 msec |
Short circuit current: |
|
8 kA |
Time of switch (manual /automatic): |
|
<0.1 ms / <6 ms (typical 3 ms) |
Level of increased voltage: |
|
+ 6 / 9 / 13 / 16 / 20% |
Level of decreased voltage: |
|
- 8 / 12 / 16 / 20 / 24% |
Phase difference (for synchronized inputs): |
|
8 / 12 / 16 / 20 / 24 degrees |
Switch at current overload: |
|
block is absent / 3 / 4,5 / 6 / 7,5 / 9-fold overload |
Switch delay (without synchronization): |
|
13 / 17 / 25 / 50 msec |
Delay of reset to priority input: |
|
0,8 / 1 / 8 / 25 sec |
Conditions: Temperature |
|
0 - 40°C |
Conditions: Relative humidity |
|
<95% without condensation |
Conditions: Level above sea |
|
1000 m (more than 1000 m power reduce by 5%) / 500 m / not more than 3000 m |
Conditions: Cooling |
|
back-up fans |
Conditions: Noise level |
|
<55 dBA |
Conditions: IEC |
|
EN50022 level B, EN60555-23 |
Conditions: Design |
|
IP20 (floor-mounted cabinets), IP00 (19’’ case) |
Alarm: Dry contacts |
|
300 V or 250 V-/ 0,3 A = 4 or A-(at 220) |
Alarm: Status Information |
|
manual switch, return blockage, main/back-up input ОК, main/back-up input ON |
Alarm: Notifications |
|
main/back-up of input out of tolerance, no synchronization, manual mode |
Alarm: Emergency alarms |
|
overload, overheat, fuse actuated, internal accident of STS | |
150А
3-pole, floor-mounted cabinet (H х W х D), mm: |
|
|
3-pole, 19’’ case (H х W х D), mm: |
|
|
4-pole, floor-mounted cabinet (H х W х G), mm: |
|
|
4-pole, 19’’ (H х W х D), mm: |
|
710 x 483 x 465 |
Weight (approximatey), kg: |
|
195 |
Color: |
|
RAL 7032 |
Rated input voltage: |
|
3 х 400 V |
Input voltage range: |
|
-25% / +20% |
Rated frequency: |
|
50 Hz |
Frequency range: |
|
-9% / +6% |
Efficiency coefficient: |
|
> 99% at cos? = 0,8 |
Allowable cross ratio: |
|
3,5 : 1 |
Power factor (max. cos?): |
|
0.5 – 1.0 (delay /advance) |
Overload capability: |
|
125% - hour, 400% - 5 seconds, 800% - 0.4 sec, 1000% - 0.2 sec, 1500% - 20 msec |
Short circuit current: |
|
8 kA |
Time of switch (manual /automatic): |
|
<0.1 ms / <6 ms (typical 3 ms) |
Level of increased voltage: |
|
+ 6 / 9 / 13 / 16 / 20% |
Level of decreased voltage: |
|
- 8 / 12 / 16 / 20 / 24% |
Phase difference (for synchronized inputs): |
|
8 / 12 / 16 / 20 / 24 degrees |
Switch at current overload: |
|
block is absent / 3 / 4,5 / 6 / 7,5 / 9-fold overload |
Switch delay (without synchronization): |
|
13 / 17 / 25 / 50 msec |
Delay of reset to priority input: |
|
0,8 / 1 / 8 / 25 sec |
Conditions: Temperature |
|
0 - 40°C |
Conditions: Relative humidity |
|
<95% without condensation |
Conditions: Level above sea |
|
1000 m (more than 1000 m power reduce by 5%) / 500 m / not more than 3000 m |
Conditions: Cooling |
|
back-up fans |
Conditions: Noise level |
|
<55 dBA |
Conditions: IEC |
|
EN50022 level B, EN60555-23 |
Conditions: Design |
|
IP20 (floor-mounted cabinets), IP00 (19’’ case) |
Alarm: Dry contacts |
|
300 V or 250 V-/ 0,3 A = 4 or A-(at 220) |
Alarm: Status Information |
|
manual switch, return blockage, main/back-up input ОК, main/back-up input ON |
Alarm: Notifications |
|
main/back-up of input out of tolerance, no synchronization, manual mode |
Alarm: Emergency alarms |
|
overload, overheat, fuse actuated, internal accident of STS | |
250А
3-pole, floor-mounted cabinet (H х W х D), mm: |
|
1900 x 800 x 500 |
3-pole, 19’’ case (H х W х D), mm: |
|
|
4-pole, floor-mounted cabinet (H х W х G), mm: |
|
1900 x 1200 x 500 |
4-pole, 19’’ (H х W х D), mm: |
|
710 x 483 x 465 |
Weight (approximatey), kg: |
|
195 |
Color: |
|
RAL 7032 |
Rated input voltage: |
|
3 х 400 V |
Input voltage range: |
|
-25% / +20% |
Rated frequency: |
|
50 Hz |
Frequency range: |
|
-9% / +6% |
Efficiency coefficient: |
|
> 99% at cos? = 0,8 |
Allowable cross ratio: |
|
3,5 : 1 |
Power factor (max. cos?): |
|
0.5 – 1.0 (delay /advance) |
Overload capability: |
|
125% - hour, 400% - 5 seconds, 800% - 0.4 sec, 1000% - 0.2 sec, 1500% - 20 msec |
Short circuit current: |
|
15 kA |
Time of switch (manual /automatic): |
|
<0.1 ms / <6 ms (typical 3 ms) |
Level of increased voltage: |
|
+ 6 / 9 / 13 / 16 / 20% |
Level of decreased voltage: |
|
- 8 / 12 / 16 / 20 / 24% |
Phase difference (for synchronized inputs): |
|
8 / 12 / 16 / 20 / 24 degrees |
Switch at current overload: |
|
block is absent / 3 / 4,5 / 6 / 7,5 / 9-fold overload |
Switch delay (without synchronization): |
|
13 / 17 / 25 / 50 msec |
Delay of reset to priority input: |
|
0,8 / 1 / 8 / 25 sec |
Conditions: Temperature |
|
0 - 40°C |
Conditions: Relative humidity |
|
<95% without condensation |
Conditions: Level above sea |
|
1000 m (more than 1000 m power reduce by 5%) / 500 m / not more than 3000 m |
Conditions: Cooling |
|
back-up fans |
Conditions: Noise level |
|
<55 dBA |
Conditions: IEC |
|
EN50022 level B, EN60555-23 |
Conditions: Design |
|
IP20 (floor-mounted cabinets), IP00 (19’’ case) |
Alarm: Dry contacts |
|
300 V or 250 V-/ 0,3 A = 4 or A-(at 220) |
Alarm: Status Information |
|
manual switch, return blockage, main/back-up input ОК, main/back-up input ON |
Alarm: Notifications |
|
main/back-up of input out of tolerance, no synchronization, manual mode |
Alarm: Emergency alarms |
|
overload, overheat, fuse actuated, internal accident of STS | |
400А
3-pole, floor-mounted cabinet (H х W х D), mm: |
|
1900 x 1200 x 500 |
3-pole, 19’’ case (H х W х D), mm: |
|
|
4-pole, floor-mounted cabinet (H х W х G), mm: |
|
2100 x 1200 x 600 |
4-pole, 19’’ (H х W х D), mm: |
|
710 x 483 x 465 |
Weight (approximatey), kg: |
|
280 |
Color: |
|
RAL 7032 |
Rated input voltage: |
|
3 х 400 V |
Input voltage range: |
|
-25% / +20% |
Rated frequency: |
|
50 Hz |
Frequency range: |
|
-9% / +6% |
Efficiency coefficient: |
|
> 99% at cos? = 0,8 |
Allowable cross ratio: |
|
3,5 : 1 |
Power factor (max. cos?): |
|
0.5 – 1.0 (delay /advance) |
Overload capability: |
|
125% - hour, 400% - 5 seconds, 800% - 0.4 sec, 1000% - 0.2 sec, 1500% - 20 msec |
Short circuit current: |
|
25.5 kA |
Time of switch (manual /automatic): |
|
<0.1 ms / <6 ms (typical 3 ms) |
Level of increased voltage: |
|
+ 6 / 9 / 13 / 16 / 20% |
Level of decreased voltage: |
|
- 8 / 12 / 16 / 20 / 24% |
Phase difference (for synchronized inputs): |
|
8 / 12 / 16 / 20 / 24 degrees |
Switch at current overload: |
|
block is absent / 3 / 4,5 / 6 / 7,5 / 9-fold overload |
Switch delay (without synchronization): |
|
13 / 17 / 25 / 50 msec |
Delay of reset to priority input: |
|
0,8 / 1 / 8 / 25 sec |
Conditions: Temperature |
|
0 - 40°C |
Conditions: Relative humidity |
|
<95% without condensation |
Conditions: Level above sea |
|
1000 m (more than 1000 m power reduce by 5%) / 500 m / not more than 3000 m |
Conditions: Cooling |
|
back-up fans |
Conditions: Noise level |
|
<55 dBA |
Conditions: IEC |
|
EN50022 level B, EN60555-23 |
Conditions: Design |
|
IP20 (floor-mounted cabinets), IP00 (19’’ case) |
Alarm: Dry contacts |
|
300 V or 250 V-/ 0,3 A = 4 or A-(at 220) |
Alarm: Status Information |
|
manual switch, return blockage, main/back-up input ОК, main/back-up input ON |
Alarm: Notifications |
|
main/back-up of input out of tolerance, no synchronization, manual mode |
Alarm: Emergency alarms |
|
overload, overheat, fuse actuated, internal accident of STS | |
630А
3-pole, floor-mounted cabinet (H х W х D), mm: |
|
2100 x 1200 x 600 |
3-pole, 19’’ case (H х W х D), mm: |
|
|
4-pole, floor-mounted cabinet (H х W х G), mm: |
|
2300 x 1200 x 600 |
4-pole, 19’’ (H х W х D), mm: |
|
710 x 483 x 465 |
Weight (approximatey), kg: |
|
280 |
Color: |
|
RAL 7032 |
Rated input voltage: |
|
3 х 400 V |
Input voltage range: |
|
-25% / +20% |
Rated frequency: |
|
50 Hz |
Frequency range: |
|
-9% / +6% |
Efficiency coefficient: |
|
> 99% at cos? = 0,8 |
Allowable cross ratio: |
|
3,5 : 1 |
Power factor (max. cos?): |
|
0.5 – 1.0 (delay /advance) |
Overload capability: |
|
125% - hour, 400% - 5 seconds, 800% - 0.4 sec, 1000% - 0.2 sec, 1500% - 20 msec |
Short circuit current: |
|
39 kA |
Time of switch (manual /automatic): |
|
<0.1 ms / <6 ms (typical 3 ms) |
Level of increased voltage: |
|
+ 6 / 9 / 13 / 16 / 20% |
Level of decreased voltage: |
|
- 8 / 12 / 16 / 20 / 24% |
Phase difference (for synchronized inputs): |
|
8 / 12 / 16 / 20 / 24 degrees |
Switch at current overload: |
|
block is absent / 3 / 4,5 / 6 / 7,5 / 9-fold overload |
Switch delay (without synchronization): |
|
13 / 17 / 25 / 50 msec |
Delay of reset to priority input: |
|
0,8 / 1 / 8 / 25 sec |
Conditions: Temperature |
|
0 - 40°C |
Conditions: Relative humidity |
|
<95% without condensation |
Conditions: Level above sea |
|
1000 m (more than 1000 m power reduce by 5%) / 500 m / not more than 3000 m |
Conditions: Cooling |
|
back-up fans |
Conditions: Noise level |
|
<55 dBA |
Conditions: IEC |
|
EN50022 level B, EN60555-23 |
Conditions: Design |
|
IP20 (floor-mounted cabinets), IP00 (19’’ case) |
Alarm: Dry contacts |
|
300 V or 250 V-/ 0,3 A = 4 or A-(at 220) |
Alarm: Status Information |
|
manual switch, return blockage, main/back-up input ОК, main/back-up input ON |
Alarm: Notifications |
|
main/back-up of input out of tolerance, no synchronization, manual mode |
Alarm: Emergency alarms |
|
overload, overheat, fuse actuated, internal accident of STS | |